Product Type: DIN Rail Mounted High VAC/VDC to Logic Level Converter, Inputs: 4 85-130 VAC/VDC

Price
$1,098.00 CAD
Stock
17 In Stock

Specifications

Approvals & Certifications

  • CE
  • CSA
  • FM
  • IEC Ex
  • UL

Enclosure, Body Material

  • ABS Plastic

Configuration Method

  • Two latching pushbuttons for selection of output State inversion and cascade mode selection. No other Programming Required.

Indicators

  • One Green Power LED. Four Red LED indicators to monitor live Inputs on channels 1-4. Two Yellow LED indicators for inverted output and/or cascade output mode.

Input Channels

  • Four independent, isolated Input channels CH1 to CH4

Input Voltage Threshold

  • Input high Voltage levels are different for AC and DC Voltages. Instantaneous value is used to determine threshold for AC Input - RMS Equivalents are shown below.

PDA1500-115Input High Threshold Range

  • 60 Vac RMS (85 Vac peak) or 85 Vdc

Input Low Threshold Range

  • 31 Vac RMS (44 Vac peak) or 44 Vdc

PDA1500-230Input High Threshold Range

  • 131 Vac RMS (185 Vac peak) or 185 Vdc

Input Current

  • 1.2 mA (Typical) at ”turn-On” or High Input Voltage

Propagation Delays

  • Input Propagation Delay to Logic Low: 4 µs (Typ), 15 µs (Max.), Input Propagation Delay to Logic High: 8 µs (Typ), 40 µs (Max.).

Input Impedance

  • PDA1500-115: > 60k Ω total impedance per channel, PDA1500-230: > 140k Ω total impedance per channel.

Input Overload

  • Must not exceed 50 mA DC (35 mA RMS) on Input channels. Max. Input Power dissipation is 230 mW. Surge Protection included for up to 140 mA. Transient Protection included for up to 500 mA.

Digital Outputs

  • Four TTL Logic (5 V) independent digital outputs.

Output Logic Levels

  • Output Low: 0 to 0.33 V
  • Output High: 4.4 to 5.0 V

Cascade Mode

  • Typically used in Boiler applications to monitor for and detect Fault conditions.

Power

  • 12-24 Vdc + 10 %, 1.5 W Max. Polarity Sensitive. Short-Circuit Protected. Isolated.

Maximum Power Dissipation

  • PDA1500-115: 3 W (Total dissipation of unit) PDA1500-230: 4 W (Total dissipation of unit)

Isolation

  • 630 VRMS between Input channels, 3750 VRMS Input-to-Power line, 3750 VRMS Input-to-output, 1000 VRMS output-to-Power line

Overvoltage

  • Maximum overvoltage (Transient) Allowable is 6000 V peak for 60 seconds

Environmental

  • Operating Temperature Range: 0 to 65° C

Storage Temperature Range

  • 0° to 65° C

Relative Humidity

  • 0 to 90 % Non-Condensing

Connections

  • Fixed Screw terminal blocks accept 12 to 30 AWG solid or stranded wire.

Enclosure

  • DIN Rail-mountable ABS plastic Enclosure. Color: Black

DIN Rail Specification

  • 35 mm ”top hat” DIN Rail Required

Tightening Torque

  • Screw terminal Connectors: 4.3 lb-in (0.56 Nm)

Overall Dimensions

  • Inch (mm) 3.00” x 3.63” x 2.38” (76.3 mm x 92.3 mm x 60.5 mm)(W x H x D)

Weight

  • 12 oz. (340.2 g)

Warranty

  • 1 Year
show more