Approvals & Certifications
- CE
- EMC Compliance to EN 55011,EN 55022 (CISPR22) Class B, EN 61000-3-2,-3 EN 61000-4-2, 3, 4, 5, 6, 8, 11, ENV 50204, EN 55024, EN 61000-6-1, EN 61204-3 Light Industry, Criteria A
Output Voltage
- 21.6-26.4 Vdc, ± 10 % 1.5 A rated Current. See output rating table below
AC Current
- 115 Vac: 0.88 A, 230 Vac: 0.48 A
Inrush Current
- 115 Vac: 15 A, 230 Vac: 30 A Cold Start
Connections
- Two Screw terminals for +V, two Screw terminals for V-
Setup, Rise Time
- 115 Vac: 100 ms, 30 ms, 230 Vac: 100 ms, 30 ms at full load
Hold Time
- 115 Vac: 21 ms, 230 Vac: 100 ms, 30 ms at full load
Overload Protection
- 105-160 % Rated output Power. Constant Current limiting, recovers automatically after Fault condition is removed
Over Voltage Protection
- Shut down o/p Voltage, re-Power on to recover
Operating Temperature
- -20° to 60° C (-4° to 140° F)
Working Humidity
- 20 % to 90 % Relative Humidity, Non-Condensing
Storage Temperature, Humidity
- -40° to 85° C (-40 - 185° F), 10 % to 95 % Relative Humidity
Temperature Coefficient
- ± 0.03 %/°C (0° to 50° C)
Vibration
- 10-500 Hz, 2G 10 min./1 cycle, period for 60 min. each along X, Y, Z axes
Safety Standards
- UL 60950-1, TUV EN 60950-1 Approved, Design refer to EN 50178
Isolation Resistance
- I/P-O/P: 100 Mohms / 500 Vdc
EMC
- Compliance to EN 55011,EN 55022 (CISPR22) Class B, EN 61000-3-2,-3 EN 61000-4-2, 3, 4, 5, 6, 8, 11, ENV 50204, EN 55024, EN 61000-6-1, EN 61204-3 Light industry, Criteria A
MTBF
- 441.5K hours min. MIL-HDBK-217F (25° C)
Dimensions
- 3.07” x 3.66” x 2.20” (78 mm x 93 mm x 56 mm) (W x H x D)