Model 25 Reversing Relay
Brand: Fairchild Industrial ProductsThe Rotork Fairchild Model 25 Reversing Relay is designed for applications requiring an output that equals a manually preset spring load minus a variable signal pressure.
This high quality unit combines excellent sensitivity with unusually high flow capacity.
The Model 25 is ideally suited for a variety of precision control applications, including converting direct acting valves to reverse action, controlling opposite acting valves from a single transmitter, and cushioning cylinder loads.
The basic mathematical expression for the Model 25 is PO = K - PS where PO is output pressure, PS is signal pressure and K is the spring constant.
Features- Control Sensitivity of 1/8" water column
- Balanced supply valve
- Aspirator tube design
- Separate control chamber isolates
- Unit construction
- Allows for use in high precision applications
- Minimizes the effects of supply pressure variation
- Compensates for output pressure droop under flow conditions
- Isolates the diaphragm from the main flow to eliminate hunting and buzzing
- Allows servicing without removal from air line
Specifications
Actuator Type
- Knob Adjust
Ambient Temperature Range
- -40° to 93° C (-40° to 200° F)
BSP Connection
- BSPP Female (Parallel)
- BSPT Female (Tapered)
Elastomers
- Buna-N on Dacron
- Fluorocarbon (Viton)
Enclosure, Body Material
- Aluminum
Exhaust Capacity - Relieving Units Only
- 11 scfm (18.7 m³/hour)
Flow Capacity
- 40 scfm (68 m³/hour)
Mounting
- Panel Mount
- Pipe
NPT Connection
- 1/2” NPT Female
- 1/4” NPT Female
- 3/8” NPT Female
Pressure Range
- bar: 0 to 0.7
- bar: 0.03 to 2
- bar: 0.1 to 4
- bar: 0.15 to 10
- kPa: 0 to 70
- kPa: 10 to 400
- kPa: 15 to 1,000
- kPa: 3 to 200
- psi: 0.5 to 30
- psig: 1 to 60
- psig: 2 to 150
Relief
- Relieving
Sensitivity
- < 1/8” WC (0.32 cm)
Signal or Output Pressure - Maximum
- bar: 10
- kPa: 1,000
- psig: 150
Supply Pressure - Maximum
- bar: 17
- kPa: 1,700
- psig: 250
Supply Pressure Effect
- psig: 0.1 (bar: 0.007, kPa: 0.7) for a psig: 100 (bar: 7, kPa: 700) Change in Supply Pressure
Vent
- Straight