The ConsoliDator+ is a multi-channel controller that is both easy to use and satisfies a wide variety of process display, alarm and control applications.
It accepts 4-20 mA inputs, flow meter pulse inputs, digital inputs, and Modbus RTU inputs and displays them both in numeric and bar graph format on a large, 5.7" color display.
It can be equipped with multiple relays with user-definable actions, 4-20 mA outputs, digital outputs, Modbus RTU, and Ethernet Modbus TCP/IP protocol communication capabilities.
Additionally, the controller is equipped with up to 32 timers that can be used to control many processes or events.
Features
NEMA 4X Panel Mount Multi-Channel Controller
Convenient Display, Control, & Alarm of Multiple 4-20 mA & Pulse Inputs
Numeric & Bar graph Color Display (320 x 240 pixels) 5.7" (145 mm)
Sunlight Readable Display, White Backlight
Isolated 24 VDC Transmitter Supplies 200 mA / Analog Input; 1,600 mA Max
User selectable units or custom units Time, Distance, Volume, Pressure, Weight, Temperature, Current, Voltage, Percent, Amps, Volts, Counts, Logic, and Custom, Any unit/unit of time or other units
Display Update Rate
User selectable: 0.1 to 10 sec (10 updates/ sec to 1 update/10 sec)
Programming Method
Front Panel Buttons, external Buttons, or ConsoliDator+ Software
Number of Alarms
Up to 64 high or Low Automatic (non-latching) or latching on & Off time delays. May be assigned to one or more Relays. Note: Alarms are independent from Relays.
Alarm Types
Single Source: One Input
Multi-Source: Two or more Inputs
Interval: Enter time interval and on Time
Alarm OR: Any active Input Alarm triggers the OR Alarm
Alarm AND: All Input Alarms must be active to trigger the AND Alarm
Alarm Ack & Reset
Automatic only (Non-latching)
Manual only (Latching)
Manual with Ack only after Alarm is Cleared (Latching with Clear)
Automatic and manual
Internal Buzzer
60 dBA @ 24 inches (61 cm) Enable/disable in System - General menu. Associated with Alarm Horn setting
External Horn (Sold Separately)
Assign any Relay to the Horn function to activate an external horn when Alarm condition is detected.
Calibration
All Inputs and outputs are calibrated at the factory. Field calibration not possible.
Input & Output Cards
Maximum Number of I/O Cards: 7
Analog Inputs: 4/card
Pulse Inputs: 4/card
Analog Outputs: 5/card
Relays: 5/card
Number of Screens
Up to 20 screens with 1 to 8 PVs or items per screen. Enable or disable screen title, channel #, and bargraph Automatic or manual scanning Scan Time: 1 to > 1000 sec, independent for each screen. F1-F4 keys are assigned per screen
Function Keys
User Programmable (See defaults below) F1 = Previous ← F2 = Next → F3 = Scan/Stop F4 = Ack
Number of Channels
Up to 99 channels Input source: 4-20 mA, Pulse, Digital, Modbus, Alarm, Math, Channel, Total, Timer, mA Output, Relay Output, Digital Output, or Modbus Output
Password
Programmable password restricts modification of programmed settings
Non-Volatile Memory
Settings stored for a minimum of 10 Years
Power (User Selectable Based on Wiring)
47 to 63 Hz
60 W max DC: 113-370 Vdc
60 W max (L, N)
Two-terminal Connector (G, 24 V) DC: 24 Vdc ± 10 %, 60 W max
AC: 80-264 Vac
Three-terminal Connector (L, N, GND)
Back-Up Power Supply
If AC and DC Power are Connected, the 24 Vdc can be used as backup Power in Case of AC Power failure.
Fuse
Unit is Protected internally with auto-Resettable fuse. AC: 1.25 A max., DC: 3.7 A max
External Fuse
Recommended external fuse slow-blow 120 Vac: 2.0 A, 240 Vac: 1.0 A, 24 Vdc: 4 A
Isolation & Grounding
1500 V Analog Inputs/outputs-to-Power line, 500 V Analog Input-to-input, Input-to-output, analog output-to output
All analog Inputs and analog outputs are isolated from each other. Note: DC Power is not isolated. DC- is Connected to Earth Ground. Digital I/O, USB, and Ethernet are grounded.
Environmental
Operating Temperature Range: -40 to 60° C (-40 to 140° F)
Storage Temperature Range: -40 to 60° C (-40 to 140° F)
Relative Humidity: 0 to 90 % Non-Condensing
*All functions operate down to -40° C (-40° F.) If the LCD response is slower, increase the display refresh setting
Connections
Removable Screw terminal blocks
Digital I/O: 16 to 30 AWG
RS-485: 12 to 24 AWG wire RJ45 Ethernet Connection