Q476 Field Configurable Isolator
Brand: EurothermThe Q476 is a DIN rail mount, frequency input signal conditioner with 1,800 Vdc isolation between input, output and power.
The field configurable input and output offers flexible, wide ranging capability for variable frequency drives, magnetic pickups, turbine flowmeters, and other pulse or frequency output transducers.
The input of the Q476 can be configured for any frequency span from 2 to 10,000 Hz.
The input amplitude threshold sensitivity can be adjusted from 150 mVp to 10 Vp to ensure accurate frequency measurement and minimize transient noise related errors.
The maximum input amplitude is 150 Vrms.
The output can be set for either 0 to 5 V, 0 to 10 V, 0 to 1 mA, 0 to 20 mA or 4-20 mA.
Features- Eliminates ground loops
- Field configurable input ranges 2 to 10,000 Hz
- Field configurable output ranges
- 150 mV to 150 V Input amplitude
- TouchCAL technology
- DIN rail mounting with IQRL
- Universal AC power 85 to 265 Vac
- SnapLoc plug-in terminals
Specifications
Brand
Accuracy
- ± 0.1 % at 25° C (77° F)
Applications
- Control Systems
- Industrial Data Acquistion
- Magnetic Pickups
- Turbine Flow Meter Monitor
Approvals & Certifications
- CSA C22.2 - File No. LR42272
- IEC 801-2
- UL (C,US)
- UL 508 (File No. E99755)
Current
- Excitation Voltage (Short Circuit, Max.
Display
- LEDs
Electrical Connectors
- Plug-In Terminal
- Wire Termination: Screw Terminals for 12 to 22 AWG
Electrical Contacts
- Normally Closed
Electrical Rating
- 0-1 mA at 7.5 V, Max.
- 0-20 mA at 12 V, Max.
Electromagnetic Rating
- ESD Protection
Excitation Voltage
- 8 Vdc for Open Collector & Contact Closure Input
Frequency
- Input (Full Scale Range:) 2 to 10,000 Hz
- Over-Range: 20 kHz, Max.
Humidity
- Operating: 15 to 95 % Non-Condensing at 45° C (113° F)
- Soak: 90 % Non-Condensing for 24 Hours at 65° C (149° F)
Hysteresis
- ± 0.1 % at 25° C (77° F)
Input
- 150 mV-150 V
- Common Mode: 1,800 V, Max.
- Overvoltage: 180 Vrms, Max.
Input Impedance
- > 10 kiloohms
- Output Current (Source Impedance): > 100 kiloohms
- Output Voltage (Source Impedance): < 100 ohms
Isolation
- 1,800 Vdc between Input, Output & Power
Linearity
- ± 0.1 % at 25° C (77° F)
Mounting
- DIN Rail Mounting
Operating Temperature
- 0° to 55° C (32° to 131° F)
Output
- ± 0.1 %, Max.
- 0-10 V
- 0-20 mA
- Voltage Drive: 10 mA - Max.
Power
- 100-240 Vac ± 10 %, 50/400 Hz
- 2.5 W, Max.
- Universal AC Power: 85-265 Vac
Response Time
- 10 to 90 %: 500 milliseconds or 100 times the Period of the Full Scale Frequency
Sensitivity
- 1 Vrms
Span & Zero Effect
- Turn-Up, Turn-Down: 99 % of Full Scale (2 Hz, 9,998 Hz)
Stability
- ± 0.025 %/°C, Max.
Storage Temperature
- -25° to 70° C (-13° to 158° F)
Switch Type
- DIP Switches
Update Time
- 20 minutes