OPTIBAR P 3050 C Pressure Transmitter

Brand: Krohne

With its industry standard process connections the OPTIBAR P 3050 C is universally used for general-purpose pressure applications. 

The transmitter features superb accuracy over a wide temperature and pressure range, compact stainless steel housing, rapid response times and outstanding reproducibility and long term stability. 

These features are made possible by using sensors which are extremely stable across a wide range of temperatures and pressure ranges. 

Additional digital compensation reduces the temperature dependence on the pressure measurement.
Features
  • Robust design with internal stainless steel diaphragm
  • Vacuum and overpressure resistant versions for absolute and gauge pressure
  • Very short response times (< 50 ms)

Specifications

Brand

Accuracy

  • Measuring Accuracy: ± 0.1 % of Measuring Span

Alarm

  • High Alarm: 21 mA
  • Low Alarm: 3.6 mA

Ambient Pressure

  • psi: 14.8 to 15.4 (kPa: 102 to 106.2, bar: 1.02 to 1.06)

Ambient Temperature Range

  • Ambient Temperature (Constant): 18° to 30° C (64° to 86° F)

Applications

  • Absolute & Gauge Pressure Measurement of Gases, Vapours & Liquids
  • Automation
  • Hydrostatic Level Measurement in Containers
  • Iron & Steel
  • Water & Wastewater

Approvals & Certifications

  • CE
  • EMC Conformity for EN 61326-1
  • NAMUR NE 43

BSP Connection

  • G 1/2”-B to DIN EN 837-1

Cable Entry

  • M16 x 1.5

Cable Material

  • 316L Stainless Steel
  • M16” Plastic
  • Nickel-Plated Brass

Cable Type

  • 2 Twisted Double Wire

Damping Adjustment

  • 0.1 second

Diaphragm Material

  • 316L Stainless Steel, 1.4401

Display

  • LCD Graphic Display with 4 Push Buttons

Electrical Connectors

  • 20 AWG Twisted

Enclosure Finish

  • Grey

Enclosure, Body Material

  • 316L Stainless Steel

Environmental Protection

  • IP65
  • IP67

Fill Material

  • Silicone Oil

Gasket Material

  • EPDM

Gland Material

  • Nickel Plating Brass
  • Plastic

Humidity

  • 30 to 80 % Relative Humidity (Constant)

Materials of Construction

  • Sensor Tag: Stainless Steel

Mounting Position

  • Any Orientation

NPT Connection

  • 1/2”-14 Female NPT
  • 1/2”-14 Male NPT

Operating Pressure

  • Absolute: psi a: 0 to 2,900 (kPa: 0 to 20,000, bar: 0 to 200)
  • Gauge: psig: 0 to 290 (kPa: 0 to 2,000, bar: 0 to 20)

Operating Temperature

  • Blind Version: -40° to 85° C (-40° to 185° F)
  • LCD Graphic Display: -20° to 70° C (-4° to 158° F)

Output

  • 4-20 mA, 2-Wire

Pressure Type

  • Absolute
  • Gauge

Process Temperature

  • -40° to 85° C (-40° to 185° F)

Resolution

  • 128 x 64

Response Time

  • 50 milliseconds (Including Dead Time)

Stability

  • ≤ ± 0.1 % of URL within 1-Year

Storage Temperature

  • -20° to 70° C (-4° to 158° F)

Supply Voltage

  • 12-45 Vdc

Temperature Range

  • -40° to 105° C (-40° to 221° F)

Update Time

  • 10 seconds

Wetted Materials

  • ANSI 316L Stainless Steel, 1.4401

show more