Q488 Input Field Configurable Isolator

Brand: Eurotherm

The Q488 is a DC powered, DIN rail mount, RTD, thermocouple, mV or Ohm input signal conditioner with 1,800 V isolation between input, output and power. 

The field configurable input and output offers flexible, wide ranging capability for most temperature signal conditioning applications.

The Q488 is configured via DIP switch for the thermocouple type (B, C, E, J, K, N, R, S, T) or the RTD type (Pt, Ni and Cu). 

Additionally, functions such as signal linearization, up or down scale burnout, number of RTD leads (2, 3, 4) and voltage or current output are also set via dip switches.
Features
  • Instant accuracy
  • Field configurable input ranges
  • PC or DIP switch configuration
  • Eliminates ground loops
  • TouchCAL technology
  • High density DIN rail mounting
  • Flexible DC power supply 9 to 30 Vdc
  • SnapLoc plug-in terminals

Specifications

Accuracy

  • ≤ ± 10 µA for Current Output
  • ≤ ± 5 mV for Voltage Output
  • Input (A/D): ± 1 ohm
  • Input (A/D): ± 12 μV
  • Input (A/D): ± 25 μV
  • RTD (A/D): ± [0.15° to 0.25° C (0.27° to 0.45° F)]
  • Thermocouple (A/D): ± [0.25° to 2° C (0.45° to 3.6° F)]

Applications

  • SCADA Systems

Approvals & Certifications

  • CSA C22.2 - File No. LR42272
  • IEC 801-2
  • UL (C,US)
  • UL 508 (File No. E99755)

Burn-Out

  • Downscale
  • Upscale

Display

  • LEDs

Electrical Connectors

  • Plug-In Terminal
  • Wire Terminal: Socketed Screw Terminals for 12 to 22 AWG

Electrical Contacts

  • Normally Closed

Electromagnetic Rating

  • ESD Protection

Humidity

  • Operating: 15 to 95 % Non-Condensing at 45° C (113° F)
  • Soak: 90 % Relative Humidity, Non-Condensing for 24 Hours at 60° C (140° F)

Input

  • -900 to 900 mV
  • RTD Excitation: ≤ 0.3 mA

Input Impedance

  • ≥ 1 Megaohm Typical for Thermocouple & mV Inputs

Isolation

  • 1,800 Vdc or Peak AC between Input, Output & Power

Linearization

  • ≤ ± 0.05 % of Accuracy Range, Max.

Mounting

  • DIN Rail Mounting

Operating Temperature

  • -25° to 65° C (-13° to 149° F)

Output

  • 0-10 V
  • 0-20 mA
  • Current Drive: 15 V (750 ohms, Max.
  • Voltage Drive: 10 mA (1,000 ohms Load Min.)

Power

  • 2.5 W, Max.

Power Supply

  • Flexible DC: 9-30 Vdc ± 10 %

Resistance

  • Input: 0 to 4,000 ohms

Response Time

  • 400 milliseconds Typical

RTD Type

  • Cu9
  • Ni120
  • Pt100
  • Pt1000
  • Pt200
  • Pt500

Sensor, Probe Type

  • B Thermocouple
  • C Thermocouple
  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • N Thermocouple
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple

Span - Minimum

  • 0 to 4,000 ohms: 10 ohms
  • -900 to 900 mV: 3 mV

Span & Zero Effect

  • Thermal Stability: ± 0.0075 % of Full Scale/°C Change in Ambient, Max.

Stability

  • Thermal Stability (CJC): ± 0.01° C/°C Change in Ambient, Max.
  • Thermal Stability (Long Term): ± 0.1 %, Max.

Storage Temperature

  • -25° to 70° C (-13° to 158° F)

Switch Type

  • DIP Switches

Temperature Range

  • RTD (Input Range): -200° to 850° C (-328° to 1,562° F)
  • Thermocouple (Accuracy Range): -100° to 2,320° C (-148° to 4,208° F)
  • Thermocouple: -270° to 2,320° C (-454° to 4,208° F)

Turn-On Time

  • ≤ 5 seconds to Establish Output within 99 % or 0.5° C of Final Value