PD138 MINIMUX II Temperature and Process Scanner

Brand: Precision Digital Corporation

The MINIMUX® II PD138 is a microprocessor-based, eight-channel analog input scanner/multiplexer and annunciator that provides low-cost automatic switching for multi-point display and alarm systems. 

It can automatically switch up to eight inputs to another device such as a digital panel meter, controller, or PLC. 

Signal switching is done via reed relays making the PD138 ideal for switching thermocouples, RTDs, control loops, and AC/DC signals. 

They feature rugged NEMA 4X/IP65 fronts and a wide operating temperature range. 

They can be programmed for many common ISA alarm sequences including first out indication and they provide alarm signaling through front panel LEDs and a build in 85 dB horn.
Features
  • 8 Inputs per Unit, Eliminates Need for 7 Displays
  • Unlimited Number of Units per System
  • Free Custom Message Labels
  • Thermocouples, RTDs, Process, AC & DC Inputs
  • Adjustable Dwell Time for Each Channel
  • Independent Alarm Input for Each Channel
  • First-Out Alarm Indication
  • Alarms Indicated by LEDs, Built-in Horn, and Relay
  • Built-in 85 dB Horn with Silence Pushbutton
  • Stop-On-Alarmed Channel (Field Select)
  • Non-Interruptible 4-20 mA Inputs
  • Sunlight Readable Indication
  • NEMA 4X/IP65 Front
  • Shallow Depth 1/8 DIN Enclosure
  • -40° to 65°C Operating Temperature Range

Models matching criteria: 6
  • Power - 230 Vac
  • Resistor - Without Resistor
100+ In Stock
$412.00 CAD
$10.00 Shipping
  • Power - 24 Vdc
  • Resistor - Without Resistor
50+ In Stock
$892.00 CAD
$10.00 Shipping
  • Power - 24 Vdc
  • Resistor - With Loop Resistor
25+ In Stock
$1,681.00 CAD
$10.00 Shipping
  • Power - 230 Vac
  • Resistor - With Loop Resistor
15 In Stock
$2,282.00 CAD
$10.00 Shipping
  • Power - 115 Vac
  • Resistor - Without Resistor
11 In Stock
$1,869.00 CAD
$10.00 Shipping
  • Power - 115 Vac
  • Resistor - With Loop Resistor
2 In Stock
$1,368.00 CAD
$10.00 Shipping

Specifications

Input

  • 8-Channels

Enclosure, Body Material

  • High Impact Plastic

Environmental Protection

  • IP65
  • NEMA 4X

Resistance

  • 0.2 ohms

Operating Temperature

  • -40° to 65° C (-40° to 150° F)

Storage Temperature

  • -40° to 85° C (-40° to 185° F)

Humidity

  • 0 to 90% RH Non-Condensing

Maximum Power Switched

  • 10 W

Power Supply

  • 15 VAC, ± 10%, 50/60 Hz, 4 VA
  • 230 VAC, ± 10%, 50/60 Hz, 4 VA
  • 12-24 VDC (9-18 VAC, 50/60 Hz) 2 W

Maximum Current Switched

  • 0.5 A

Maximum Input Voltage

  • 200 V (Switched or Common Mode)

Certifications & Approvals

  • UL

show more